NOTES: Abovementioned distances are measured from the outside edge of an aboveground tank or from the filling connection or the relief valve of an underground or mounded tank.
6.11. Separation distances may be reduced by the provision of a fire wall in accordance with the following rules:
The minimum distance between the tank and the fire wall is 1.5 m.
Where a fire wall is constructed, the separation distance shall be calculated by adopting the following formula:
A = A + B (m)
Where:
D: minimum separation distance indicated in Table 1;
A: distance measured horizontally from the tank to the gable of the fire wall;
B: distance measured horizontally from the above-determined gable of the fire wall to the adjacent structure (housing or office building, etc.)
...
...
...
Mọi chi tiết xin liên hệ: ĐT: (028) 3930 3279 DĐ: 0906 22 99 66
Figure 1. Separation distance from a tank with a fire wall
6.12. Fire walls are normally used on one side of a tank or tank grouping. Fire walls should not be used on more than two sides of tank grouping or where the ventilation would be impaired.
6.13. LPG tanks and oxygen containers must be sited according to the separation distances in Table 2.
Table 2 - Separation distances between LPG tanks and liquid oxygen containers
Capacity of liquid oxygen container (m3)
Capacity of LPG tank (m3)
Separation distance (m)
...
...
...
Mọi chi tiết xin liên hệ: ĐT: (028) 3930 3279 DĐ: 0906 22 99 66
Up to 2.5 m3
6
From 2.5 m3 to 9.0 m3
7,5
9.0 m3 or above
15
125 m3 or above
...
...
...
Mọi chi tiết xin liên hệ: ĐT: (028) 3930 3279 DĐ: 0906 22 99 66
30
5.0 m3 or above
45
The adjacent ends of the cylindrical tanks designed for horizontal installation shall be separated from each other in a row; they must be installed parallel with ends in line and must not be directed toward housing or service buildings. Aboveground tanks shall be installed in groups. The number of tanks in one group depends on the fire protection system and is provided for in Table 3.
Table 3 – Maximum number of aboveground tanks in one group
Fire protection provided by
Maximum number of tanks in one group (tanks)
Minimum separation distances between groups (m)
...
...
..
Để xem đầy đủ nội dung và sử dụng toàn bộ tiện ích của Hệ Thống Pháp Luật vui lòng lựa chọn và đăng ký gói cước.
Nếu bạn đã là thành viên, hãy bấm:
National Standard TCVN 6486:2008 for Liquefied petroleum gas ("LPG") - Pressurised storage - Requirements for design and location of installation
- Số hiệu: TCVN6486:2008
- Loại văn bản: Tiêu chuẩn Việt Nam
- Ngày ban hành: 01/01/2008
- Nơi ban hành: ***
- Người ký: ***
- Ngày công báo: Đang cập nhật
- Số công báo: Đang cập nhật
- Ngày hiệu lực: 01/05/2026
- Tình trạng hiệu lực: Kiểm tra